Lead exits are special insulation systems used in large power transformers high voltage side to lead conductors through tank walls from the windings to the bushing in high safety factors. Lead exit design is based on an electrode as a metal core insulated by high quality formed transformer board with several numbers of barriers. The number of barriers depends on maximum field stress in the oil gaps and it is designed with consideration of maximum safety factors.